Home | Our Mission | ElectrAtest Lounge
 
   Search For: 
 
Services

Portable Appliance Testing (PAT)
Fixed Wiring/Periodic Inspection
Certification
FM Companies
Technical
Software and Data
Labelling
Megger PAT4 Tester
Related Information
Downloadable Documents (PDF)
Client List
What Are Portable Appliances?
Frequency of Testing
Traceability & Quality Assurance
Your Questions Answered
FAQ
Company Policies
Legal Notice
Privacy Statement
Further Information
Links
Picture Gallery
Contact
Enquiry Form
Contact ElectrAtest
 
 

UNDERTAKING

The intention of this document is to provide an undertaking, the requirements of which are set down in the:

Electricity at Work Regulation 1989
British Standards No. 7671
I.E.E. Guidance Note No. 3 2nd Edition Part 2

SCOPE OF WORK

The scope of the work is to give a professional opinion of the installations condition by carrying out visual inspections and instrument test of those parts of the Fixed Wiring Installation which are accessible.

The test and inspections would comprise:


Characteristics of supply at the origin of the installation.
Visual inspection.
C.P.C. continuity test.
Ring Circuit Continuity
Insulation resistance test.
Polarity check.
Earth fault loop impedance test.
Prospective short circuit currents.
Operation of residual current devices.

CHARACTERISTICS OF SUPPLY (Reg. 313-01-01)

The characteristics of supply at the origin of the installation would be determined and would include the following:

Nominal voltage.
Nature of current and frequency.
Prospective short circuit current.
External earth fault loop impedance. (Ze)
Maximum demand in amps.
Type of rating of supplier's overcurrent protective device.

VISUAL INSPECTION (Reg. 731-01-02)

Inspection comprising careful scrutiny of every installation, where required, shall be carried out in accordance with the requirements of this chapter.

The safety of the persons and livestock against the effects of electric shock and burns, in accordance with Regulations 120-01, and
Protection against damage to property by fire and heat arising from an installation defect, and
The identification that the installation is not damaged or deteriorated so as to impair safety, and
On a sampling basis, check that conductors are readily identified in accordance with Reg. 514-03, and tables 51A and 51B.
No signs of overloading of conductors and accessories.
On a sampling basis, check correct connection of socket outlets and Lampholders including: -

(a) Protective conductors installed and sleeved green/yellow.
(b) Protective conductor installed between back box and Socket earth terminal.
(c) No sharp edges that may cause mechanical damage to Cable insulation.
(d) No undue mechanical strain on cables.
(e) Conductors readily identifiable.
(f) No excessive removal of insulation.

Presence of fire barriers including:

(a) Trunking is constructed of non-combustible material and covers are securely fixed.
(b) Fire barriers are fitted in vertical trunking and rising bus-bar systems.
(c) Holes surrounding cable, conduit and trunking are sealed to an Appropriate degree of fire resistance.

Presence of appropriate devices for isolation and switching as follows:

(a) Isolation.
(b) Switching off for mechanical maintenance.
(c) Emergency switching (where applicable).
(d) Functional switching.


Choice and setting of protective devices to include:-

(a) Fuses/MCB's/Circuit breakers are of correct type and rating for intended use.
(b) Tabulated current rating of cables is equal to or greater than Setting of protection device.

Labelling of circuits, fuses, switches, distribution boards, terminals etc. to indicate its purpose.

Presence of danger notices and other warning notices such as:

(a) Warning notices on equipment where 250 volts is exceeded (Reg. 514-10-01).
(b) Warning notices on earthing and bonding conductors stating "Safety Electrical Connection - Do Not Remove". (Reg. 514-13-01).

Identifying dangers, which might arrive during instrument testing.

Flexible cables and cords (Reg 712-01-03). Where a flexible cable or cord forms part of the fixed wiring installation, the inspection should include:

(a) Examination of the cable or cord for damage or defects.
(b) Examination of the terminations and anchorage's for damage or defects.
(c) The correctness of its installation with regard to additional mechanical protection, heat resistant sleeving, etc.

Enclosures and Mechanical Protection (Reg. 713-07-08, 712-01-03). The enclosure and mechanical protection of all electrical apparatus and equipment should be inspected to ensure that their condition remains adequate for type of protection needed.

External influences. (Reg. 712-01-02, 712-01-03) Note should be made of any known changes in external influences, building structure, and alterations or additions which may have affected the suitability of the wiring for its present load and method of
installation.

Note should be made of any alterations for additions of an irregular nature to the installation. If unsuitable material has been used the Report should indicate this together with reference to any evident faulty workmanship or design.

Presence of diagrams, instructions and similar information (Reg. 514-09-01). Where sample inspections are carried out, these should include removal of luminaire covers, switch plates, socket outlets and covers of equipment.

Its is neither practicable nor possible to inspect all parts of the Installation and a sampling process would be employed, normally in the order of 10% of all accessories, lighting fittings and control equipment.

The installation would not be dismantled in any other way other than opening equipment covers and the building structure would not be disturbed. This means that concealed cables and equipment would not be inspected.

C.P.C. CONTINUITY (Reg. 713-02-01)

Protective conductors would be tested to verify that the conductors are Electrically sound and correctly connected.

This test should include:

(a) All bonding conductors.
(b) All earth visible clamps.
(c) All metal accessories and equipment within a height of 3.5m above floor level.
(d) The last lighting point on all lighting circuits.

The results of C.P.C. continuity tests shall be recorded in ohms.

RING CIRCUIT CONTINUITY (Reg 713-03-01)

An abbreviated ring circuit loop test would be carried out which will only ascertain that there is a ring on the outgoing cables from the distribution board and shall not identify a bridged ring.

INSULATION RESISTANCE (Reg. 713-04)

Insulation resistance tests between phase conductors, neutral and earth, and excepting any electronic equipment which may be damaged by the test, would be carried out to verify that the insulation of conductors, electrical accessories and equipment is satisfactory and that electrical conductors or protective conductors are not short circuited, or show a low resistance which would indicate deterioration in the insulation.

The test would be carried out with all fuses in place, switches and circuit breakers closed, and other equipment disconnected as appropriate.

Where the removal of lamps and/or the disconnection of current using equipment is impracticable, the local switches controlling such lamps and/or equipment would be open.

Insulation resistance tests would be carried out from all main switchboards and sub-main cables.

At distribution boards, insulation resistance tests would be carried out at the bus-bars and would include all final circuits connected to the distribution board, tested collectively.


POLARITY (Reg. 713-09-01)

A test of polarity would be carried out to verify that fuses and single pole control devices are connected in the phase conductor only.

The polarity on lighting circuits and equipment would be carried out on a 10% random sampling basis. The polarity on socket outlets on a 100% basis.


EARTH FAULT LOOP IMPEDANCE (Reg. 713-10-01)

Measurements would be made of the earth fault loop impedance at the main intake, all switchboards, distribution boards and bus-bar systems.

On lighting circuits 10% (on a random basis) of all luminaries, with a minimum of one luminaire, preferably the furthest one from the dis-board, for each circuit of the installation.

The earth fault loop impedance would be measure at all accessible 13 amp General purpose socket outlets and fixed equipment where visible. (See over).

Where final circuits comprise a number of different wiring systems from the original of the installation, an approximation of the loop impedance under fault conditions shall be carried out in accordance with I.E.E. Guidance No. 3, 'INSPECTION AND TESTING'.

If the measured value of loop impedance does not exceed 83% of the relevant values in Tables 41B1 and 41B2, this would be considered satisfactory and disconnection times will be achieved.

A satisfactory result is indicated on the appropriate test sheet by 'P' and an unsatisfactory result by 'F'.

Should the approximation exceed the tabulated value, a full and more accurate calculation shall be carried out for that circuit.

In order that these maximum values can be directly compared with the actual test values, it is necessary to adjust the tabulated figures since these are based on a conductor temperature under fault conditions (70ºC for PVC) and the test results are based on a conductor temperature taken as the ambient temperature (20ºC).

The calculation is a follows:-


Zs = {F (Zs -Ze)} + Ze (max) (TAB)

WHERE Zs
(MAX) = Value indicated on test sheet 4 for direct comparison with the measured value.

Zs
(TAB) = Value given in I.E.E. Regs. Tables 41B1, 41B2 and 41D.

Ze = External earth fault loop impedance at origin.

F = Correction factor to adjust tabulated value to a Conductor temp of 'ambient' for direct comparison with test value.

The test sheet would include a column headed "Max E.F.L.I." in which is indicated maximum earth fault loop impedance for each circuit tested to achieve disconnection times of 5 sec. Or 0.4 sec. As applicable, this information is indicated.

These values should be based on Tables 41B1 and 41B2 and 41D of the I.E.E. Wiring Regulations and related to the time/current characteristics of the protective device in the circuit.


PROSPECTIVE SHORT CIRCUIT CURRENT (Reg. 434-02-01)

The prospective fault current, under both short-circuits and earth fault conditions, at every relevant point of the complete installation shall be determined. This shall be done by calculation, ascertained by enquiry or by measurement.

OPERATION OF RESIDUAL CURRENT DEVICES (Ref. 713-12-01)

Where protection against indirect contact is provided by a residual current device, its effectiveness shall be verified by a test simulating an appropriate fault condition and independent of any test facility incorporated in the device.

The test would be made on the load side of the device, between the phase conductor of the circuit protected and the associated C.P.C., so that a suitable residual current flows. All loads normally supplied through the device would be disconnected during the test.

General purpose rcds to Bs 4293

(a) with a fault current flowing equivalent to 50% of the rated tripping current of the rcd for a period of 2 s, the device should not be open
(b) with a fault current flowing equivalent to 100% of the rated tripping current of the rcd, the device should open in less than 200 ms.

General purpose rcds to BS EN 61008 or rcbo's to BS EN 61009

(a) with a fault current flowing equivalent to 50% of the rated tripping current of the rcd for a period of 2 s, the device should not open
(b) with a fault current flowing equivalent to 100% of the rated tripping current of the rcd, the device should open in less than 300 ms unless it is of "Type S" (or selective) which incorporates an intentional time delay. In this case it should trip within the time range of 130 ms and 500 ms.

RCD protected socket-outlets to BS7288

(a) with a fault current flowing equivalent to 50% of the rated tripping current of the rcd for a period of 2 s, the device should not open
(b) with a fault current flowing equivalent to 100% of the rated tripping current of the rcd, the device should open in less than 200 ms.

Additional requirements for supplementary protection (Ref. 412-06-02). Where the rcd is used to provide supplementary protection against direct contact in accordance with Regulation 412-06-02, with a test current of 150 mA the device should open in less than 40 ms. The maximum test time must not be longer than 50 ms.

Since some residual current devices are either partially desensitised or totally disabled by waveforms containing a pulsating D.C. component, the instrument used would have a D.C. test facility which should cause the device to trip within 200 ms.

All the above tests would be carried out at phase angles of 0º and 180º.

In no event should test currents be applied for periods exceeding two seconds.

The effectiveness of the test button or other test facility integral with the device would be tested after application of the externally applied tests described above.


DOCUMENTATION (Chapter 74)

On completion, certified documentation would be provided including all instrument reading.

(a) SHEET A - Particulars of installation including supply characteristics and main earthing and bonding details.

The report shall be set out as follows:

All items individually numbered.
The location of the remedial item stated.

All items of remedial works shall include the I.E.E. Regulation Reference number of which they are in breach.
All items of remedial work shall be marked on site for ease of location with a sticker.
Each item of remedial works would be classified with a reference letter as follows:

A - REQUIRES IMMEDIATE ATTENTION

B - REQUIRES URGENT ATTENTION

C - REQUIRES ATTENTION AS SOON AS PRACTICABLE - COULD DETERIORATE AND BECOME A DANGER

D - REQUIRED TO BRING INSTALLATION INTO LINE WITH CURRENT STANDARDS OF GOOD WORKMANSHIP AND PRACTICES


LABELS

All distribution boards tested would be provided with an adhesive label, fixed to the front cover indicating the date tested.

Software

We have decided to create out own software for Fixed Wiring inspections. This software will be available to purchase.

PIRForm is a new software package to provide electricians a low cost, easy to use method of producing Periodic Installation Reports for fixed wiring installations. For more information, please visit the PIRform website.


Electrical Appliance Testing - Electrical Inspection and Testing - Electrical Installation Testing - Nationwide PAT Testing
PAT Testing - Portable Appliance Testing - Applicance Testing - Electrical Certification - Electrical Inspections
Electrical Safety Certificate - Electrical Testing - PAT Testing Regulations